MEDIUM VOLTAGE INSTRUMENT TRANSFORMERS

Compact range up to 24kV - 2 HV bushings

v7p v24p

This range can be split into 2 parts:

  • Vts insulated up to 12 kV: V12P & V12G
  • Vts insulated for 24kV: V24P & V24G

You can find the different models for each requirement in the following chart (click on the name to see the drawing):

insulation
kV
BIL
kV
 MAXIMUM primary voltage
V
Type MAXIMUM possible burden (VA) Thermal burden (VA)
1 secondary 2 secondaries
class 0.2 class 0.5 class 1.0 cl. 0.5
+
cl.0.5
cl. 1.0
+
cl.1.0
7.2 60
6600 V12P 15 50 100 15 + 15 30 + 30 250
12 75 11000 V12P 15 50 100     250
V12G 30 100 200 50 + 50 100+100 400
24 125 22000 V24P 10 50 100     300
V24G 50 150 400 50 + 50 100+100 700

Secondary voltage: 110 or 100 V, other values on request.

The voltage factor is 1.2Un permanent for all models.